Tuesday, 1 July 2014

Audiometric Booth

Bhaskar India   
                                                               
                                                                          

(Authorized OEA for Kirloskar Electric Bliss Generator)                                

Mktg off- Bldg No-83,Sector-6 Vaishali

Regd Off & Works- RN-26, B Block Sector-62, Noida-201301

Gensets,  Accoustic, Audiometeric booth
Tel : 95120-  4210541.4126790, 9911801118
Fax : 95120-  2405348     
U.P.T.T.NO : ND0330813
TIN NO        : O9366201529

C.S.T     NO : ND5327453

Website-: www.bhaskarindia1.com               

TECHNICAL SPECIFICATION OF AUDIOMETRIC ROOM CONSTRUCTION

        CONSTRUCTION

v The Audiometric Booths are modular in construction.
v Outer Panel Surface1.6 mm CRCA Sheet
v Inner panel Surface: G.I. perforated sheet 0.7 mm thick.
v Floor shall be 50mm thick with 3.0 mm MS Sheet upper surface and 1.6mm MS sheet for lower Surface
Completely Insulated with Sound Damping material, all floor are Carpeted

ACCOUSTIC FELT


v For floors, walls, door and roof panels shall be sound retardant, absorbing, inert, and Mildew resistant and
vermin proof. Heat transfer factor shall be no more than 0.397 Wm C.
v High Density, Asphalt Free, Visco-Elastic, Sound Block Membrane to be applied for Sound Proofing in floor & Panel.
v Covering with fire proof tissue paper.

WINDOW CONSTRUCTION

v Windows shall be 750mm x 600mm (sizes may vary in some orientations), double glazed, using 6.0mm thick
laminated safety glass.

ELECTRICAL

v All booths are provided with lighting operated from an adjacent switch. Power operation 240V, 50Hz.
v Led Maintenance free ceiling Recessed lights.
v Ceiling panel contains an HSE silenced forced ventilation system.

JACK PANEL

v A jack panel consisting of nine, 6.4 mm three-pole jack sockets shall be provided below the window.
This jack panel shall be designed and installed to preserve the acoustic integrity of the booth.

DOOR CONSTRUCTION

v One 650 mm wide X 1780 mm high (clear opening) for complete safety and effective acoustic   Control,
Compression seals are mounted on the top, bottom and sides of the door leaf

PAINT FINISH

v Zinc passivity hardware is used to avoid rusting.
v All Audiometric Room is Off white Powder Coated Finish (Or customer Choice)




DIMENSIONS

v  Outer Dimensions: 1200mm (L), 1200mm (W), 2400mm (H)
v  Inner Dimensions:  1000mm (L), 1000mm (W), 2150mm (H)

        PERFORMANCE SPECIFICATION

Frequency
63
125
250
500
1 Khz
2 Khz
4Khz
8Khz

Db (A)
33
31
39
50
57
61
68
62
NIC 51
Sound Absorption Coefficient
0.38
0.94
1.19
1.11
1.06
1.03
1.03
1.04
NRC 0.95